Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO.
If you cannot find what you are looking for please
submit a records request.
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date |
Description |
Inspector |
Results |
Comments |
| 01/07/2004 |
ELECTRIC - INTERMEDIATE |
|
Approved |
IVRS - Inspection 0000* |
| 12/30/2003 |
ELECTRIC - INTERMEDIATE |
|
Partial Approval |
IVRS - Inspection 0000*/ 1) INSTALL CONDUIT TO CODE AND USE PROPER CONNECTORS 2) JUNCTION BOX IN ATTIC-TIGHTEN CONNECTOR AND BOND JUNCTION BOX 3) INSTALL MISSING COVER PLATES 4) GROUND METAL BOXES |