Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/03/2004 | PLUMBING - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 06/18/2004 | PLUMBING - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999*/ 1) MUST PROVIDE ISOLATORS FOR 1" WTR THAT PENETRATES THRU METAL STUDS. 2) CAN NOT USE A 3" SAN CROSS FOR BACK TO BACK WTR CLOSETS. THIS MUST BE A DBL FIXTURE FITTING OR THE BARREL OF THE SAN CROSS MUST BE 2 PIPE SIZE LARGER. 3) OK TO DRYWALL 1ST FLOOR. |
|
| 06/16/2004 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :*/ 1) PROVIDE WTR TEST ON WASTE AND VENT FROM 4" SEWER EXISTING THRU ROOF ON ALL FIXTURES. 2) PROVIDE FIG 5 AT BACK TO BACK STOOLS. 3) ISOLATE COPPPER FROM ALL METAL WITH TEN MIL TAPE. 4) PROVIDE HANGERS AT 4' INTERVALS ON ALL HORIZONTAL PLASTIC PIPE. 5) SECURE ALL PIPING USING APPROVED METHODS. - TIE WIRE IS NOT. 6) PROVIDE HANGERS AT CORRECT INTERVALS ON ALL HANGING PIPING. |