Permit: T03CM05846

Parcel: 140250570


Addresses:

1050 E MILTON RD 01

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
10/03/2005 ELECTRIC - FINAL Approved IVRS - Inspection :*
09/30/2005 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
09/26/2005 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999* PLANS CALL FOR 20A TOGGLES IN UNITS FOR SWITCHING. REVISE PLANS TO REFLECT ACTUAL INSTALLL FOR PANEL SIZE & RATINGS, WIRE SIZES. GROUND ALL LIGHT SWITCHES, LEAVE ?? OFF FOR INSPECTION. PROVIDE LETTER OF TORQUE FOR SERVICE. LABEL ALL PANELS SWITCHES. NEED TO INSTALL BUSHINGS OR BUSHED CONNECTIONS IN GUTTER ABOVE SERVICE.