Inspection History: PLUMBING - INTERMEDIATE
Permit Number - T03CM05845
Inspection Description - PLUMBING - INTERMEDIATE
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/29/2005 | PLUMBING - INTERMEDIATE | Approved | IVRS - Inspection :* 1) OVERHEAD WATER TEST IS OK. 2) OVERHEAD WATER DISTRIBUTION IS OK. 3) OK FOR DRYWALL. | |
| 06/28/2005 | PLUMBING - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) OVERHEAD WATER DISTRIBUTION IS OK. 2) UNIT # 202 HAS A SAN TEE FOR THE FLAT VENT @ SHOWER SHALL PROVIDE A DIRECTIONAL FITTING. 3) UNIT # 201 HAS EXCEEDED 135 DEGREE CHANGE OF DIRECTION FOR 2" LAV WASTE |