Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
Permit Number - T03CM05844
Inspection Description - PLUMBING - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/02/2004 | PLUMBING - INTERMEDIATE | Approved | IVRS - Inspection 0000* | |
01/22/2004 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection 0000*/ PLEASE PROVIDE GAS PERMIT. | |
01/21/2004 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*/ 1) ABS DWV THRU ROOF OK. CONTRACTOR TO INSURE WATER TIGHTNINGS - WET FROM RAIN? 2) COPPER WATER PIPING OK. CLOSET FLANGES OK. 3) OK TO COVER ALL AREAS. 4) WATER HEATER NOT INSTALLED PER 94 UPC. SEE 511.2 94 UPC - LOCATION. EXPANSION TANK TO BE SUPPORTED. DRAIN PAN REDUCING FROM 1" TO 3/4" CONSIDERED AN OBSTRUCTION. | |
01/20/2004 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection 0000* | |
01/16/2004 | PLUMBING - INTERMEDIATE | Partial Approval | 1) ABS UNDERGROUND OK - INSTALLED PER REVISED APPROVED PLAN. 2) OK TO COVER. 3) CONNECTION TO EXISTING OK. |