Inspection History Details
Inspection Status: Denied
Inspection History: MECHANICAL - FINAL
Permit Number - T03CM05806
Inspection Description - MECHANICAL - FINAL
Inspection Status - Denied
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/28/2007 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* PROVIDE A FILTER IN FRESH AIR INTAKE |
|
09/18/2007 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* - PROVIDE A FILTER IN THE FRESH AIR INTAKE - SECURE CONDENSATE DRAINS TO WALL & PAINT W/LATEX PAINT |
|
11/22/2005 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999*TERMINATE CONDENSATE DRAINS WITHIN 6" OF THE GROUND. EXTEND GUARD RAIL 30'' BEYOND SIDE OF A/C UNIT & SUPPORT GUARD RAIL. PROVIDE A FRESH AIR INTAKE ON S.W UNIT. PERMANENTLY IDENTIFY ALL A/C UNITS. |
|
11/23/2004 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :*1)TWO UNITS ON SOUTH SIDE-CENTER OF BLDG. A)5 TON PKG. HT. PUMP. ROMOVE ELECT. SWITCH ,LOCKED OFF, OUT OF SERVICE-BLOCKING CLEAR ACCESS TO COMPRESSOR COMPARTMENT B)SHORTEN SUPPLY DUCT (10"X8") 3=BLOCKING REAR ACCESS PANEL 3 TON COMB. UNIT. 2)SOUTH WEST PLG. HT. PUMP, 36,000 BTUH. UNIT LOCATED 24" FROM EDGE OF 5/12 PITCH ROOF. A)IMC 306.5 NEED TO PROVIDE LEVEL PLATFORM AT REAR OF UNIT FOR SERVICE B)TERMINATE CONDENSATE DRAIN PROPERLY C)COMPLETE DATA PLATE - AUX. HT. STRIP? YES? NO? WHAT? MARK IT! 3)NUMBER I.D. ALL UNITS |