Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T03CM05806
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/23/2004 | ELECTRIC - FINAL | Approved | IVRS - Inspection :*/ 1) ALL A/C WORK APPEARS TO BE COMPLETE | |
07/16/2004 | ELECTRIC - FINAL | Denied | IVRS - Inspection :DENIED. (1) NOT ALL AC UNITS CONNECTED. (2) UNIT WITH 2 DISCONNECTS (ONE NOT TERMINATED, ONE CONNECTED HAS HOLE REAR WALL). (3) MECHICAL, PLUMBING AND BUILDING FINALS ALSO REQUIRED FOR C OF O. (4) TIGHTEN ALL LOOSE FLEX CONNECTIONS TO AC'S. See detailed listing on site.| 999* |
|
04/13/2004 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection 0000*/ 1) OK TO CLEAR INCREASE 2) ALL CONDUITS WHICH CARRY NON PROTECTED CONDUCTORS REQUIRE A GROUND BUSHINGS FOR STURDIER GROUNDING 250.94, STANDARD LOCK NUTS ARE INSUFFICIENT ON THEIR OWN 3) ROOF A/C UNIT (WEST) COND PUMP 208V 5 AMP RUN ON IT'S OWN. DISCONNECT FOR A/C UNIT WHICH PROTECTED AT 30 AMPS REMOVE FEED FROM THIS DISCONNECT 4) NOTE TO MUCH 5 UNITS ON ROOF NOT CONNECTED |