Permit: T03CM05803

Parcel: 138243610


Addresses:

6637 S LUXOR WY

Inspection Status: Approved

Inspection History: FRAMING

Date Description Inspector Results Comments
02/11/2004 FRAMING Approved IVRS - Inspection 0000*
02/10/2004 FRAMING Denied IVRS - Inspection 0999*/ 1) FHA STRAPS FOR OVER NOTCHED PLATES REQUIRE 6-16D NAILS EACH END-NOT DRYWALL SCREWS (GAS) 2) TRUSS BRACING NOT INSTALLED 3) GAS LINE NOT PROPERLY SUPPORTED AND CLAMPED 4) OVERSPAN-STUD MISSING LAUNDRY 5) HALL TRAP WEIR CONNOT BE HIGHER THEN VENT OPENING AT LAV 6) REVERSE PITCH HALL W/C VENT 7) A/C COPPER NOT IN 8) A/C CONDENSATES NOT IN