Permit: T03CM05788

Parcel: 133163020

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Permit Number - T03CM05788

Inspection Description - MECHANICAL - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
12/10/2004 MECHANICAL - FINAL Approved IVRS - Inspection :*/OK FOR FINAL
12/08/2004 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*/USE CHASE NIPPLES ON DISCONNECTS. DO NOT UISE WHITE WIRES IN DISCONNECTS. TIGHTEN LOOSE FITTINGS
12/06/2004 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*/ 1) LEVEL A/C UNITS
2) PROVIDE SUPPORTS ON ELECTRIC DISCONNECTS
3) TIGHTEN LOOSE SEAL ? CONNECTIONS
4) IDENTIFY THE UNGROUNDED CONDUCTORS
5) USE A BUSHING OR CHASE NIPPLE WHERE DISCONNECT IS MOUNTED TO UNIT
6) DISCONNECT CANNOT BE MOUNTED SIDEWAYS
7) PROVIDE DISCONNECTING MEANS FOR CONDENSORS ON ROOF WITH PROPER CONDUIT AND FITTINGS
8) PERMANENTLY IDENTIFY A/C UNITS
9) REMOVE KINKS FROM REFER LINES