| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/10/2004 | MECHANICAL - FINAL | Approved | IVRS - Inspection :*/OK FOR FINAL | |
| 12/08/2004 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999*/USE CHASE NIPPLES ON DISCONNECTS. DO NOT UISE WHITE WIRES IN DISCONNECTS. TIGHTEN LOOSE FITTINGS |
|
| 12/06/2004 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999*/ 1) LEVEL A/C UNITS 2) PROVIDE SUPPORTS ON ELECTRIC DISCONNECTS 3) TIGHTEN LOOSE SEAL ? CONNECTIONS 4) IDENTIFY THE UNGROUNDED CONDUCTORS 5) USE A BUSHING OR CHASE NIPPLE WHERE DISCONNECT IS MOUNTED TO UNIT 6) DISCONNECT CANNOT BE MOUNTED SIDEWAYS 7) PROVIDE DISCONNECTING MEANS FOR CONDENSORS ON ROOF WITH PROPER CONDUIT AND FITTINGS 8) PERMANENTLY IDENTIFY A/C UNITS 9) REMOVE KINKS FROM REFER LINES |