Permit: T03CM05788

Parcel: 133163020

Inspection Status: Approved

Inspection History: MECHANICAL - INTERMEDIATE

Permit Number - T03CM05788

Inspection Description - MECHANICAL - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
07/27/2004 MECHANICAL - INTERMEDIATE Approved IVRS - Inspection :*APPROVED. OK FOR SHEET ROCK.
07/15/2004 MECHANICAL - INTERMEDIATE Denied IVRS - Inspection :
A reinspection fee has been assessed for this inspection. Multiple inspection. Provide scrren in all exhaust t-tops. Secure exhaust duct at roof to keep from falling out. Block around fan housings or use the brackets supplied with the fans. Provide condensate drains as per plans. Provide the revision to mechanical plans. Install fan coil in unit #301. All above corrections are noted on a previous inspection and have not been addressed.
07/08/2004 MECHANICAL - INTERMEDIATE Denied IVRS - Inspection :
A reinspection fee has been assessed for this inspection. Multiple inspection. #310-flex duct-exhaust and fan housing-not installed. #309 provide blocking, ex. fan housings. Be sure flex duct is inserted up into roof flashings. Correct/recall
07/01/2004 MECHANICAL - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*/ INSULATE ALL T-WYES AND SIDEWALL REGISTER BOXES. REPAIR OR REPLACE DAMAGED FLEX ON BATH EXHAUST. PROVIDE SCREEN IN EXHAUST T-TOPS. RECONNECT SUPPLY DUCT TO LIVING ROOM. BATHROOM EXHAUST FANS NOT PER PLANS. PROVIDE CONDENSATE DRAINS AS PER PLANS. SPLIT SYSTEM WAS NOT INSTALLED AS PER PLANS. REVISE PLANS WITH PROPER EQUIPMENT INSTALLED AND RE-SUBMIT.
06/30/2004 MECHANICAL - INTERMEDIATE Denied IVRS - Inspection :
There is no access to the site.| 920*/ NO ACCESS TO SITE. NO CONTRACTOR ON SITE.