Permit: T03CM05788

Parcel: 133163020

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
12/10/2004 ELECTRIC - FINAL Approved IVRS - Inspection :*
1) FINISH ROOF CURRECTIONS
2) OK FINAL
12/08/2004 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1) FINISH #6 OF PREVIOUS INSPECTION
12/03/2004 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*/ 1) PROTECT BULBS IN CLOSETS
2) FEEDER CABLE PULLING OUT OF SUB-PANEL
3) #8 NM CABLE TO USE BREAKER SIZED AS PER 336.26
4) ONLY ONE NEUTRAL TO A TERMINAL AND GOUNDS TO BE AS PER MANUFACTURE
5) USE APPROVED ALUMINUM SPLICES-FOR LIGHTING CIRCUIT (EXISTING) ONLY
6) GROUND ALL LIGHTS AND BRACKETS
7) BOXES AT COMBUSTIBLES TO BE FLUSH OR USE AN APPROVED EXTENDER RING-METAL NOT APPROVED. 1/4" AT NON COMBUSTIBLE
8) FULLY LAND CONDUCTOR IS NEEDED AT HOODS
9) AN APPROVED CONNECTOR IS NEEDED AT HOODS
10) INSTALL A/C DISCONNECTS AND SEAL TITE AS PER CODES
10/27/2004 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
04/27/2004 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*