Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T03CM05788
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/10/2004 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* 1) FINISH ROOF CURRECTIONS 2) OK FINAL |
|
12/08/2004 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) FINISH #6 OF PREVIOUS INSPECTION |
|
12/03/2004 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :*/ 1) PROTECT BULBS IN CLOSETS 2) FEEDER CABLE PULLING OUT OF SUB-PANEL 3) #8 NM CABLE TO USE BREAKER SIZED AS PER 336.26 4) ONLY ONE NEUTRAL TO A TERMINAL AND GOUNDS TO BE AS PER MANUFACTURE 5) USE APPROVED ALUMINUM SPLICES-FOR LIGHTING CIRCUIT (EXISTING) ONLY 6) GROUND ALL LIGHTS AND BRACKETS 7) BOXES AT COMBUSTIBLES TO BE FLUSH OR USE AN APPROVED EXTENDER RING-METAL NOT APPROVED. 1/4" AT NON COMBUSTIBLE 8) FULLY LAND CONDUCTOR IS NEEDED AT HOODS 9) AN APPROVED CONNECTOR IS NEEDED AT HOODS 10) INSTALL A/C DISCONNECTS AND SEAL TITE AS PER CODES |
|
10/27/2004 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
04/27/2004 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* |