Inspection Status: Approved
Inspection History: PLUMBING - ROUGH, SOIL
| Date |
Description |
Inspector |
Results |
Comments |
| 08/05/2004 |
PLUMBING - ROUGH, SOIL |
|
Approved |
IVRS - Inspection :* |
| 06/08/2004 |
PLUMBING - ROUGH, SOIL |
|
Partial Approval |
IVRS - Inspection :*/ 1) ABS DWV UNDERSLAB INSTALLED OK WITH ONE EXCEPTION - ABS MAY NOT BE INSTALLED IN EXPOSED EXTERIOR LOCATION. OK TO COVER. |
| 06/03/2004 |
PLUMBING - ROUGH, SOIL |
|
Not ready for Inspection |
IVRS - Inspection :*/ PLEASE HAVE YOUR PLBR ON SITE AT TIME OF NEXT INSP. CONTRACTOR TO PAY RE-INSPECTION FEE. |
| 05/25/2004 |
PLUMBING - ROUGH, SOIL |
|
Not ready for Inspection |
IVRS - Inspection :*/ NO APPROVED PLAN ON SITE. |
| 05/24/2004 |
PLUMBING - ROUGH, SOIL |
|
Not ready for Inspection |
IVRS - Inspection :*/ DOORS LOCKED - NO ACCESS. |
| 05/19/2004 |
PLUMBING - ROUGH, SOIL |
|
Not ready for Inspection |
IVRS - Inspection :*/ 1) NOT INSTALLED PER PLAN - WHERE ARE YOUR (F) P-4'S? 2) UNCOVER ALL PIPE AND EVERY FITTING. 3) DOUBLE WYE AND DOUBLE COMBO NOT PERMITTED IN THIS HORIZONTAL POSITION. INSPECTION STOPPED. |