Permit: T03CM05776

Parcel: 124061470


Addresses:

103 N PARK AV #111


Inspection Status: Approved

Inspection History: ELECTRIC - TEMPORARY SERVICE

Permit Number - T03CM05776

Inspection Description - ELECTRIC - TEMPORARY SERVICE

Inspection Status - Approved

Date Description Inspector Results Comments
11/26/2004 ELECTRIC - TEMPORARY SERVICE Approved
11/19/2004 ELECTRIC - TEMPORARY SERVICE Denied MAIN DISCONNECT GROUND WIRE LOOSE BOTTOM BRUSHING. INSTALL MAIN DISCONECT FUSES. PUT WHITE TAPE ON ALL OF GREEN WIRE USED AS A NEUTRAL @ WTR HTR DISCONNECT & TIGHTEN FITTING ON FLEX @ WTR HTR. HAVE APPROVED CHANGES ON SITE.
09/01/2004 ELECTRIC - TEMPORARY SERVICE Cancelled PER CONTRACTOR
06/09/2004 ELECTRIC - TEMPORARY SERVICE Denied IVRS - Inspection :
See detailed listing on site.| 999*/ YOU DO NOT NEED 02035 IF EVERYTHING IS SURFACE. IS THERE ANYTHING BEHIND WALLS TO LOOK AT? CABLE DROP CAN ONLY BE APPROVED IF TEMP SERVICE IS CLEARED. 1) IF RISERS ABOVE 3' OF ROOF LINE - KICKERS REQUIRED. 2) ALL MAIN DISCONNECTS HAVE TO BE PERMANENTLY ADDRESSED - METAL TAGS AND SCREWS. 3) ALL ENTRYS AND EXITS INTO METERS AND DISCONNECTS CARRYING UNPROTECTED POWER TO HAVE GROUNDING BUSHINGS AND BOND JUMPERS. 250-94, 99 NEC. 4) PLAN CHECKER DID NOT SIZE THE SERVICE ENTRANCE CONDUCTORS NOR PUT IN A GROUNDING SYSTEM FOR SERVICE, F SERVICE NOT PROVIDED ON PLAN. 5) FUSES FOR TEMP POWER REQUIRED. 6) BOND FOR TEMP POWER REQUIRED TO POSTED WITH CITY. 7) PANELS MUST BE TRIMMED AND GFI POWER SUPPLY SET UP. 8) ALL MAIN DISCONNECTS TO HAVE GREEN GROUND SCREW TO NEXT. 9) PLAN CALLS FOR 22 K AIC RATED PANELS - PLANS EXAMINER DID NOT EVEN REQUEST AIC CALCULATIONS - PANEL REQUIRES SERIES RATED SYSTEM.