Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - TEMPORARY SERVICE
Permit Number - T03CM05776
Inspection Description - ELECTRIC - TEMPORARY SERVICE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/26/2004 | ELECTRIC - TEMPORARY SERVICE | Approved | ||
11/19/2004 | ELECTRIC - TEMPORARY SERVICE | Denied | MAIN DISCONNECT GROUND WIRE LOOSE BOTTOM BRUSHING. INSTALL MAIN DISCONECT FUSES. PUT WHITE TAPE ON ALL OF GREEN WIRE USED AS A NEUTRAL @ WTR HTR DISCONNECT & TIGHTEN FITTING ON FLEX @ WTR HTR. HAVE APPROVED CHANGES ON SITE. | |
09/01/2004 | ELECTRIC - TEMPORARY SERVICE | Cancelled | PER CONTRACTOR | |
06/09/2004 | ELECTRIC - TEMPORARY SERVICE | Denied | IVRS - Inspection : See detailed listing on site.| 999*/ YOU DO NOT NEED 02035 IF EVERYTHING IS SURFACE. IS THERE ANYTHING BEHIND WALLS TO LOOK AT? CABLE DROP CAN ONLY BE APPROVED IF TEMP SERVICE IS CLEARED. 1) IF RISERS ABOVE 3' OF ROOF LINE - KICKERS REQUIRED. 2) ALL MAIN DISCONNECTS HAVE TO BE PERMANENTLY ADDRESSED - METAL TAGS AND SCREWS. 3) ALL ENTRYS AND EXITS INTO METERS AND DISCONNECTS CARRYING UNPROTECTED POWER TO HAVE GROUNDING BUSHINGS AND BOND JUMPERS. 250-94, 99 NEC. 4) PLAN CHECKER DID NOT SIZE THE SERVICE ENTRANCE CONDUCTORS NOR PUT IN A GROUNDING SYSTEM FOR SERVICE, F SERVICE NOT PROVIDED ON PLAN. 5) FUSES FOR TEMP POWER REQUIRED. 6) BOND FOR TEMP POWER REQUIRED TO POSTED WITH CITY. 7) PANELS MUST BE TRIMMED AND GFI POWER SUPPLY SET UP. 8) ALL MAIN DISCONNECTS TO HAVE GREEN GROUND SCREW TO NEXT. 9) PLAN CALLS FOR 22 K AIC RATED PANELS - PLANS EXAMINER DID NOT EVEN REQUEST AIC CALCULATIONS - PANEL REQUIRES SERIES RATED SYSTEM. |