Inspection Status: Approved
Inspection History: EXT METAL CLIPS/EXT SHEATHING
| Date |
Description |
Inspector |
Results |
Comments |
| 04/16/2004 |
EXT METAL CLIPS/EXT SHEATHING |
|
Approved |
IVRS - Inspection 0000* |
| 04/09/2004 |
EXT METAL CLIPS/EXT SHEATHING |
|
Denied |
IVRS - Inspection 0999*/ 1) NEED APPROVED TRUSS DRAWINGS 2) GROUND ALL METAL BOXES 3) NAIL OFF ROOF AND EXTERIOR SHEATHING 4) INSTALL NAIL PROTECTION ALL PLUMBING AND ELECTRIC HOLES THROUGH STUDS 5) SMOKE DETECTOR WIRING TO BE INTERCONNECTED 6) WATER TEST DWV PLUMBING SYSTEM 7) FIRE BLOCK AT CEILING LINE BETWEEN OLD AND NEW ADDITION 8) INSTALL WIRING HOME RUN FOR CLOTHES WASHER 9) BACK GROUT TUB/SHOWER PENETRATIONS THROUGH CONCRETE SLAB 10) COMPLETE ALL NEW AND REMODEL EXISTING WORK 11) MECHANICAL NOT PER PLANS 12) WILL NEED WATER HEATER ENCLOSURE 13) EXHAUST FANS NOT INSTALLED 14) STOPPED INSPECTION |
| 03/03/2004 |
EXT METAL CLIPS/EXT SHEATHING |
|
Not ready for Inspection |
IVRS - Inspection 0000* |