Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO.
If you cannot find what you are looking for please
submit a records request.
Inspection Status: Approved
Inspection History: FRAMING
| Date |
Description |
Inspector |
Results |
Comments |
| 03/29/2004 |
FRAMING |
|
Approved |
IVRS - Inspection 0000* |
| 02/26/2004 |
FRAMING |
|
Partial Approval |
IVRS - Inspection 0000*/ 1) INSTALL ATTIC DISCONNECTS FOR EACH HP 2) PARTIAL APPROVAL PENDING APPROVAL OF REVISED MECHANICAL AND ELECTRICAL PLAN AND PROPER HEAT PUMP ACCESSORY LABEL |
| 02/25/2004 |
FRAMING |
|
Denied |
IVRS - Inspection 0935*/ 1) TOP PLATE DAMAGED AND IMPROPERLY REPAIRED BY A/C COPPER 2) ITEMS 1 AND 3 FROM 2/24/04 AND PRIOR INSPECTIONS NOT COMPLIED WITH 3) GROUND ALL METAL ELECTRIC BOXES 4) LATH NOT COMPLETE AROUND OPENINGS 5) HOLDOWN NOT INSTALLED |
| 02/24/2004 |
FRAMING |
|
Denied |
IVRS - Inspection 0999*/ 1) PROVIDE ENGINEERS APPROVED REPAIR OF DAMAGED DOUBLE TOP PLATE DAMAGE OR INSTALL 4 FHA STRAPS 2 INSIDE AND 2 OUTSIDE 2) NO A/C COPPER AND CONDENSATES 3) MECHANICAL AND ELECTRIC IS NOT PER APPROVED PLAN BUILD TO PLAN OR REVISE PLAN TO AS BUILT INCLUDING MAKE, MODEL AND AMPERAGE OF AB AT PUMP AND HEAT STRIPS AND CORRECT WIRE SIZES 4) ELECTRIC NOT COMPLETE 5) SOME WINDOWS AND DOORS MISSING 6) NOT COMPLETE ENOUGH TO INSPECT |
| 02/23/2004 |
FRAMING |
|
Denied |
IVRS - Inspection 0999*/ 1) INTERIOR BEARING WALL REQUIRES STUDS 16" ON CENTER 2) DUCT BOOT NOT IN AT ENTRY 3) PROVIDE GARAGE NAILER 4) ELECTRIC NOT COMPLETE 5) REVISE MECH AND ELECT PLANS TO HEATING AS BUILT 6) COPPER AND CONDENSATE NOT IN 7) LATH NOT COMPLETE 8) FIRST FLOOR DOUBLE TOP PLATE DESTROYED ON P-1 SHEAR WALL. PROVIDE ENGINEERS APPROVED REPAIR |