Permit: T03CM05741

Parcel: 138133170

Inspection Status: Approved

Inspection History: FRAMING

Date Description Inspector Results Comments
03/29/2004 FRAMING Approved IVRS - Inspection 0000*
02/26/2004 FRAMING Partial Approval IVRS - Inspection 0000*/ 1) INSTALL ATTIC DISCONNECTS FOR EACH HP 2) PARTIAL APPROVAL PENDING APPROVAL OF REVISED MECHANICAL AND ELECTRICAL PLAN AND PROPER HEAT PUMP ACCESSORY LABEL
02/25/2004 FRAMING Denied IVRS - Inspection 0935*/ 1) TOP PLATE DAMAGED AND IMPROPERLY REPAIRED BY A/C COPPER 2) ITEMS 1 AND 3 FROM 2/24/04 AND PRIOR INSPECTIONS NOT COMPLIED WITH 3) GROUND ALL METAL ELECTRIC BOXES 4) LATH NOT COMPLETE AROUND OPENINGS 5) HOLDOWN NOT INSTALLED
02/24/2004 FRAMING Denied IVRS - Inspection 0999*/ 1) PROVIDE ENGINEERS APPROVED REPAIR OF DAMAGED DOUBLE TOP PLATE DAMAGE OR INSTALL 4 FHA STRAPS 2 INSIDE AND 2 OUTSIDE 2) NO A/C COPPER AND CONDENSATES 3) MECHANICAL AND ELECTRIC IS NOT PER APPROVED PLAN BUILD TO PLAN OR REVISE PLAN TO AS BUILT INCLUDING MAKE, MODEL AND AMPERAGE OF AB AT PUMP AND HEAT STRIPS AND CORRECT WIRE SIZES 4) ELECTRIC NOT COMPLETE 5) SOME WINDOWS AND DOORS MISSING 6) NOT COMPLETE ENOUGH TO INSPECT
02/23/2004 FRAMING Denied IVRS - Inspection 0999*/ 1) INTERIOR BEARING WALL REQUIRES STUDS 16" ON CENTER 2) DUCT BOOT NOT IN AT ENTRY 3) PROVIDE GARAGE NAILER 4) ELECTRIC NOT COMPLETE 5) REVISE MECH AND ELECT PLANS TO HEATING AS BUILT 6) COPPER AND CONDENSATE NOT IN 7) LATH NOT COMPLETE 8) FIRST FLOOR DOUBLE TOP PLATE DESTROYED ON P-1 SHEAR WALL. PROVIDE ENGINEERS APPROVED REPAIR