Permit: T03CM05738

Parcel: 112030330


Addresses:

3510 N FORGEUS AV

Inspection Status: Approved

Inspection History: FRAMING

Date Description Inspector Results Comments
07/22/2004 FRAMING Approved IVRS - Inspection :*
07/21/2004 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*/ 1) FRAMING WILL BE APPROVED WHEN ELECTRIC MEETS CODE
06/25/2004 FRAMING Not ready for Inspection IVRS - Inspection :*
06/24/2004 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*/ 1) ELECTRIC SUB-PANEL MUST HAVE IT'S OWN GROUND SEPERATE FROM MAIN PANEL 2) USE VENT TEE AT 2" VENT INTERSECTION OR CONNECT WITH SAN-TEE VERTICAL WITH SEEP UP 3) DWV SYSTEM MUST BE WATER TESTED TO TOP 4) NAIL PROTECT ALL FRAMING PENETRATIONS < 1 1/4" FROM FACE
05/14/2004 FRAMING Not ready for Inspection IVRS - Inspection :*/ 1) COMPLETE ALL TRADES PRIOR TO FRAME INSPECTION 2) ISOLATE BATH CIRCUIT 3) GROUND SUB PANEL 4) PROTECT PVC PIPE BY ELECTRIC PANEL
04/15/2004 FRAMING Not ready for Inspection IVRS - Inspection 0000*/ 1) COMPLETE ALL TRADES PRIOR TO FRAME INSPECTION
04/13/2004 FRAMING Not ready for Inspection IVRS - Inspection 0000*