Inspection History: EXT METAL CLIPS/EXT SHEATHING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/08/2004 | EXT METAL CLIPS/EXT SHEATHING | Approved | IVRS - Inspection :*/ 1) OK TO DRY IN ROOF AND EXTERIOR | |
| 06/02/2004 | EXT METAL CLIPS/EXT SHEATHING | Denied | IVRS - Inspection : See detailed listing on site.| 999*/ 1) LTT 20 B HOLDOWN REQUIRED AT EACH CORNER WITH MINIMUM OF 5/8" ANCHOR BOLT 2) EACH CORNER REQUIRES A 4 X 8 FT BRACED WALL PANEL EACH WAY 3) HOLDOWNS MUST BE CONNECTED TO DOUBLE 2 X FULL LENGTH STUDS CLIPPED TO PLATES 4) PORCH RAFTERS MUST BE CLIPPED TO BEAM 5) OVER FRAME ROOF MUST HAVE FULL LENGTH FULL WIDTH VALLEY PLATE 6) A33 ANGLE BRACKETS CANNOT BE SUBSTITUED FOR H2.5 CLIPS 7) COLLAR TIES REQUIRED ON RAFTERS IN OVER BUILD AREA. TIE IN MIDDLE 1/3 OF RAFTER TO RAFTERS AT 48" ON CENTER 8) ANCHOR BOLTS REQUIRED WITHIN 12" OF PLATE SPLICES, NOT ON SPLICES |