Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T03CM05722
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/10/2005 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* OK FINAL | |
| 02/07/2005 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :*OK TO CLERA POWER FOR TEST # 130, 230, 229, PANEL ( L) 1M | |
| 01/27/2005 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) CABLES TO BE SECURED TO PANEL ENCLOSURE 312.5 2) NEED METER FOR POOL ADDED TO PERMIT TO CLEAR. USE WHAT TEP CALLS METER ALSO MISSING UNIT #'S. OK TEMP POWER FOR TEST SUBJECT TO BOND C-125, 126, 127, 128, 129, 225, 227, 228 | |
| 01/26/2005 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) PLEASE LABEL SERVICE DISCONNECTS 2) CANNOT STACK GROUND LUGS 3) FINISH PREVIOUS ITEM | |
| 01/24/2005 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :*1) FILL UNUSED OPENING IN PANEL. 2) PLEASE LABEL PANEL CIRCUITS. 3) MAINTAIN CLEARANCE FROM EDGE OF SHELF TO FIXTURE IN CLOSET 410-8. 4) MISSING PANEL COVER # 227, 229, 230. SERVICE: 1) TIGHTEN LOOSE CONDUCTOR TERMINATIONS. 2) BONDING DEVICES NEEDED AT ALL POINTS AT SERVCE 250.94 3) PLEASE HAVE ELECTRICIAN PRESENT |