Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T03CM05722
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/03/2004 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :*/ 1) OK SERVICE FEEDERS | |
| 11/18/2004 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :*/1)FINISH SERVICE FEEDERS | |
| 11/10/2004 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :*/1)BUILDING INSPECTOR HAS NOT INSPECTED FIRE PENITRATIONS | |
| 08/25/2004 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :*/ 1) 9 UNITS, OK WALLS SUBJET TO BLDG INSPECTORS FIRE PENETRATIONS CHECK | |
| 08/20/2004 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :REPLACE BROKEN BOX NEW NM CABLES TO BE SECURED WITHIN 12" OF BOX PLEASE INSTALL FLEX FOR WATER HEATER ROUGH IN MAINTAIN FIRE SEPERATION FINISH ELECTRIC |
|
| 03/16/2004 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000* OK PANEL FEED, EXSISTING STRUCTURE OK TO USE | |
| 03/01/2004 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*/ 1) OK TO CLEAR "5220 E. BELLEVUE ST, BLDG C" 2) SENT TO TEP ON 03/02/04AM | |
| 02/27/2004 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection 0999*/ 1) ADDRESS SERVICE 2) NEED GFCI RECEPTACLE IN WASH ROOM FOR CONSTRUCTION 3) MOVE INSULATOR KNOB TO WEST SIDE OF FACIA 4) LOOSE CONDUCTOR | |
| 02/19/2004 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection 0000*/ 1) WIRE SIZED FOR 115 AMPS ONLY. NO FUSES IN DISCONNECT 2) PROVIDE LOAD CALC'S TO DETERMINE SIZE OF CONDUCTORS AND FUSES-DISCONNECT IS A 200 AMP AND PANEL IS A 200 AMP 3) REJECTION PINS NEEDED 4) PLEASE VERIFY WATER BOND 5) SERVICE CONDUCTOR CLEARANCE FROM WINDOW 230.9 6) SHEET METAL SCREWS NOT ALLOWED FOR GROUNDING 250.8 PLEASE VERIFY |