Permit: T03CM05722

Parcel: 12112051A

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T03CM05722

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
12/03/2004 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*/ 1) OK SERVICE FEEDERS
11/18/2004 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*/1)FINISH SERVICE FEEDERS
11/10/2004 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*/1)BUILDING INSPECTOR HAS NOT INSPECTED FIRE PENITRATIONS
08/25/2004 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*/ 1) 9 UNITS, OK WALLS SUBJET TO BLDG INSPECTORS FIRE PENETRATIONS CHECK
08/20/2004 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :REPLACE BROKEN BOX
NEW NM CABLES TO BE SECURED WITHIN 12" OF BOX
PLEASE INSTALL FLEX FOR WATER HEATER ROUGH IN
MAINTAIN FIRE SEPERATION
FINISH ELECTRIC
03/16/2004 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000* OK PANEL FEED, EXSISTING STRUCTURE OK TO USE
03/01/2004 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*/ 1) OK TO CLEAR "5220 E. BELLEVUE ST, BLDG C" 2) SENT TO TEP ON 03/02/04AM
02/27/2004 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection 0999*/ 1) ADDRESS SERVICE 2) NEED GFCI RECEPTACLE IN WASH ROOM FOR CONSTRUCTION 3) MOVE INSULATOR KNOB TO WEST SIDE OF FACIA 4) LOOSE CONDUCTOR
02/19/2004 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection 0000*/ 1) WIRE SIZED FOR 115 AMPS ONLY. NO FUSES IN DISCONNECT 2) PROVIDE LOAD CALC'S TO DETERMINE SIZE OF CONDUCTORS AND FUSES-DISCONNECT IS A 200 AMP AND PANEL IS A 200 AMP 3) REJECTION PINS NEEDED 4) PLEASE VERIFY WATER BOND 5) SERVICE CONDUCTOR CLEARANCE FROM WINDOW 230.9 6) SHEET METAL SCREWS NOT ALLOWED FOR GROUNDING 250.8 PLEASE VERIFY