Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T03CM05696
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/04/2004 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000*/ 1) OK FINAL | |
03/02/2004 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection 0000*/ 1) PLEASE REVISE PLANS AND LOAD CALC'S FOR CEILING CHANGE IN OFFICES 2) WHERE IS INSTA-HOT BREAKER ON PLANS ? AND DISCONNECTING MEANS 3) FILL UNUSED OPENINGS AND LABEL PANEL COVERS 4) WHERE IS BREAKER LOCK-OUT AS PER PLANS |