Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date |
Description |
Inspector |
Results |
Comments |
| 02/24/2004 |
ELECTRIC - INTERMEDIATE |
|
Approved |
IVRS - Inspection 0000* |
| 02/20/2004 |
ELECTRIC - INTERMEDIATE |
|
Denied |
IVRS - Inspection 0245*/ 1) PLEASE CORRECT THE FOLLOWING: 1) REMOVE ALL PLASTIC "TY-RAPS" FROM M CABLE. THESE ARE NOT A MANUFACTURER (MC) APPROVED SUPPORT DEVICE 2) ADD MC CABLE STRAPS TO CABLES WITHIN 12" OF BOXES 3) NEC-300-PROHIBITS THE USE OF CONDUIT OR CABLE TO SUPPORT OTHER CONDUIT OR CABLE. SUPPORT ALL RUNS INDEPENDANT OF OTHER ELECTRICAL CABLE OR CONDUIT 4) INSTALL K-O SEAL ON BOTTOM HOLE IN MAIN DISCONNECT 5) UNBUNDLE MC CABLE RUNS. BUNDLES CREATE EXCESSIVE HEAT |