Inspection Status: Approved
Inspection History: PLUMBING - SEWER HCS CONNECT
Permit Number - T03CM05692
Inspection Description - PLUMBING - SEWER HCS CONNECT
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/09/2004 | PLUMBING - SEWER HCS CONNECT | Approved | IVRS - Inspection :*/ 1) MIRROR OK MANHOLE #2-3+34+4-5 2) PROVIDE ENGINEERED VERIFICATION OF GRADE 3) PROVIDE CERTIFICATION OF COMPLIANCE FOR ADEQ. 4) BRING ALL MANHOLES TO GRADE. RESET MANHOLE #3 RING AND CLEANOUT BENCH | |
08/03/2004 | PLUMBING - SEWER HCS CONNECT | Not ready for Inspection | IVRS - Inspection :* | |
04/28/2004 | PLUMBING - SEWER HCS CONNECT | Partial Approval | IVRS - Inspection :*/ 1) 5 PSI AIR TEST FROM NEW MANHOLE IN STREET #MH 1 TO MH#2 8" DUCTILE IRON PIPE, SLEEVED, INCASED IN CONCRETE OK . MH#2 TO MH#3 8" SDR 35 INCLUDING 6" HCS FUTURE. OK 1 MH#3 TO MH #4 8" SDR 35 OK. MH#4 TO MH#5 INCLUDING 6" HCS STUBBED TO WITHIN 20' OF BLDG SEWER OK. NEED PRESSURE TEST ON 6" HCS FROM MH#4 WEST, AND 6" BLDG HCS FOR TIE IN TO BLDG AND 6" HCS FUTURE OUT OF MH#5 FUTURE | |
04/23/2004 | PLUMBING - SEWER HCS CONNECT | Partial Approval | IVRS - Inspection :*/ 6" STUB 30' SOUTH FOR FUTURE BETWEEN MH #2 AND MH #3 OK. 8" SDR 35 MH #4 TO MH #5 OK. 6" STUB 30' WEST OUT OF MH #4 OK. 6" STUB 40' WEST OUT OF MH #5 OK. NEED TO SEE 6" STUB TO BLD BETWEEN MH #4 AND MH #5 AND MEET REQUIREMENTS OF NOTES ON 4/26/04 INSP. | |
04/22/2004 | PLUMBING - SEWER HCS CONNECT | Partial Approval | IVRS - Inspection :*/ 8" SDR 35 FROM 200 WEST OF NEW M.H. #2 TO M.H. #3 INCLUDING 8X6 COMBO FOR FUTURE BLD IN THIS RUN UPSTREAM TO M.H. #4 UPSTREAM 8X6 COMBO FOR L.A. FITTINGS APP 80' NORTH OF M.H. #5 OK. PENDING CONDITIONS OF NOTES ON 4/20/04. | |
04/20/2004 | PLUMBING - SEWER HCS CONNECT | Partial Approval | IVRS - Inspection 0000*/ 20' - 8" DUCTILE IRON PIPE FROM LAST INSP, SLEEVED AND ENCASED IN CONCRETE TO MH #2 - NEW - ON YET TO BE APPROVED DRAWING - DOWN STREAM SIDE - 8" SDR 35 FROM MH #2 UPSTREAM APPROVED 200' OK. 1) WILL NEED TO SEE WTR STOP. 2) WILL NEED CITY APPROVED PLAN SHOWING THIS MH #2. 3) WILL NEED AIR TEST ON PIPING. 4) WILL NEED VERIFICATION OF GRADE ON ALL SEWER. 5) WILL NEED MANDRILL AND MIRROR OF ALL SDR PIPING. | |
04/16/2004 | PLUMBING - SEWER HCS CONNECT | Partial Approval | IVRS - Inspection 0000*/ AFTER HOURS INSP. CHECK # 3442 - $108.00./ 8" DUCTILE IRON PIPE, SLEEVED AND ENCASED IN CONCRETE FROM MIDDLE WEST LANE OF WILMOT 36' WEST TO APPROX. 15' EAST OF MH NOT SHOWN ON APPROVED PLAN TO BE RED LINED AND CITY APPROVED AT LATER DATE. PIPE IS OUT OF WILMOT. 1) WILL REQUIRE AIR TEST AT LATER DATE. 2) WILL REQUIRE VERIFICATION OF GRADE. 3) WILL REQUIRE CITY APPROVED REVISED PLAN. | |
04/15/2004 | PLUMBING - SEWER HCS CONNECT | Partial Approval | IVRS - Inspection 0000*/ AFTER HOURS INSP. CHECK # 3441 - 8" DUCTILE IRON PIPE, SLEEVED ENCASED IN CONCRETE FROM MIDDLE OF CENTER LANE, EAST SIDE OF WILMOT, APPROX. 18' WEST OF MANHOLE #1, 51' WEST TO APPROX. MIDDLE OF CENTER LANE, WEST SIDE OF WILMOT. 1) WILL REQUIRE VERIFICATION OF GRADE. 2) CITY APPROVED DRAWING SHOWING ADDITION OF MANHOLE WEST OF WILMOT. 3) WILL REQUIRE AIR TEST AT LATER DATE. | |
04/14/2004 | PLUMBING - SEWER HCS CONNECT | Partial Approval | AFTER HOURS INSPECTION CHECK #3440, $108.00. 8" DUCTILE IRON PIPE, SLEEVED INCASED IN CONCRETE PER PLAN 18' WEST OF MH 1 OK. FROM MH 1, WILL NEED: 1) TO SEE AIR TEST AT LATER DATE. 2) VERIFICATION OF GRADE ON SEWER. 3) CITY APPROVED PLAN OF ADDITION OF ONE EXTRA MANHOLE APPROX. 118' WEST OF MH 1 WHERE DUCTILE IRON PIPE ENCASED IN CONCRETE ENDS. CERTIFICATE OF CONFORMITY FROM PIMA CO. (ADEQ) TO CONSTRUCT ON SITE. ROB 891-3058. | |
03/23/2004 | PLUMBING - SEWER HCS CONNECT | Not ready for Inspection | IVRS - Inspection 0000*/ PRE-CON MTG FOR 8" SITE SEWER ACROSS WILMOT RD. |