Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T03CM05677
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/14/2005 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
01/12/2005 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
01/07/2005 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) YOU WILL NEED OUTSIDE LIGHTS INSTALLED FOR FINAL. 2) FURNACE FITTINGS IN UNITS 1-5 TO BE RETIGHTEN ALSO WH'S. 3) GARAGE NOT IN 2ND APT. 4) NEED ROOF ACCESS. |
|
01/03/2005 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :*/OK TEMP C/O. 1)OS REAR LTS 2)6102 GARAGE CEILING RECEPTACLE 3)6101 ARE FAULT BREAKER DOES NOT RESET 4)6102 MISSING TRIM CEILING FIXTURE 5)6103 TIGHTEN WH CONN 6)ALL EX FANS TO BE ON 7)NEED ROOF ACCESS | |
12/29/2004 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
12/12/2004 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :*/30AM CIR TO FURNACE PROTECTED BY 30A CB AT PANEL. FURNACE REQUIRES ONLY 30A CIR BUT HAS A 60A CB FOR DISCONNECT AT FURNACE, OR IF FURNACE HAS A LABEL FOR 30A REQUIREMENT |