Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - YARD WTR LINE/TEST
Permit Number - T03CM05675
Inspection Description - PLUMBING - YARD WTR LINE/TEST
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/13/2005 | PLUMBING - YARD WTR LINE/TEST | Approved | IVRS - Inspection :* 1) PLUMBING YARDWATER OK TO COVER | |
01/10/2005 | PLUMBING - YARD WTR LINE/TEST | Not ready for Inspection | IVRS - Inspection :*NOT READY 1) EXPOSE ALL PIPE AND ALL FITTINGS 2) PIPING IS TO BE AT LEAST 12"DEEP AT ALL POINTS. 3) PIPING IS TO BE LAID ON A FIRM BED. 4) PIPING IS TO HAVE CLEAN SHADING | |
12/23/2004 | PLUMBING - YARD WTR LINE/TEST | Not ready for Inspection | IVRS - Inspection :* | |
12/22/2004 | PLUMBING - YARD WTR LINE/TEST | Not ready for Inspection | IVRS - Inspection :* | |
05/24/2004 | PLUMBING - YARD WTR LINE/TEST | Partial Approval | IVRS - Inspection :*/ STUB IN ONLY. | |
05/10/2004 | PLUMBING - YARD WTR LINE/TEST | Partial Approval | IVRS - Inspection :*/ PARTIAL ON UNDERGROUND ROUGH. TEST ONLY ON ABS PLEASE PROVIDE SPEC. SEE HAND OUT ON BACKFLOW. |