Permit: T03CM05675

Inspection Status: Approved

Inspection History: ELECTRIC - TEMPORARY SERVICE

Permit Number - T03CM05675

Inspection Description - ELECTRIC - TEMPORARY SERVICE

Inspection Status - Approved

Date Description Inspector Results Comments
03/02/2005 ELECTRIC - TEMPORARY SERVICE Approved IVRS - Inspection :* OK TO CLEAR FUEL & TESTING POWER. OK TO CLEAR 4101, 4201, 4102, 4202, 4103, 4203, 4104, 4204 & OWNERS PANEL ( HOUSE PANEL)
01/13/2005 ELECTRIC - TEMPORARY SERVICE Denied IVRS - Inspection :
See detailed listing on site.| 999* 1) 60 AMP WIRE ON 10A BREAKER_ #6 HAS TO BE TAKEN ON 70 C COLUMN TABLE 310-16 NOT 90 BECAUSE PANEL ONLY RATED 70 TERMINATIONS. #2 OWNERS PANEL NOT FINISHED-NOT TERMINATED #3 RAIN BIRD BOX BELOW PANEL IS NOT SUPPOSED TO BE UNDER THE PANEL THE OWNER'S PANEL REQUIRES CLEARANCE BELOW IT TO GRADE