Inspection History: ELECTRIC - CABLE DROP
Permit Number - T03CM05675
Inspection Description - ELECTRIC - CABLE DROP
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/03/2004 | ELECTRIC - CABLE DROP | Approved | APPROVED BLD 4 | |
07/28/2004 | ELECTRIC - CABLE DROP | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
07/27/2004 | ELECTRIC - CABLE DROP | Not ready for Inspection | IVRS - Inspection :*/ 1) GROUND BUSHING ON RISER NEEDS BOND JUMPER TO ENCLOSURE, BECAUSE UNPROTECTED CONDUCTORS ARE GOING THRU CONCENTRIC KO'S-2002 NEC 250.94 2) LABELS FOR UNITS AND MAIN ADDRESS TO BE SCREW OR RIVITED ON PERMANENTLY CITY OF TUCSON ORD (ELECTRICAL) 3) WHERE IS NEUTRAL TO GROUND LINK ON ENCLOSURE (WHERE UFER BONDS TO CAN AND NEUTRAL) | |
07/23/2004 | ELECTRIC - CABLE DROP | Not ready for Inspection | IVRS - Inspection :* |