Permit: T03CM05675

Inspection Status: Approved

Inspection History: ELECTRIC - CABLE DROP

Permit Number - T03CM05675

Inspection Description - ELECTRIC - CABLE DROP

Inspection Status - Approved

Date Description Inspector Results Comments
08/03/2004 ELECTRIC - CABLE DROP Approved APPROVED BLD 4
07/28/2004 ELECTRIC - CABLE DROP Denied IVRS - Inspection :
See detailed listing on site.| 999*
07/27/2004 ELECTRIC - CABLE DROP Not ready for Inspection IVRS - Inspection :*/ 1) GROUND BUSHING ON RISER NEEDS BOND JUMPER TO ENCLOSURE, BECAUSE UNPROTECTED CONDUCTORS ARE GOING THRU CONCENTRIC KO'S-2002 NEC 250.94 2) LABELS FOR UNITS AND MAIN ADDRESS TO BE SCREW OR RIVITED ON PERMANENTLY CITY OF TUCSON ORD (ELECTRICAL) 3) WHERE IS NEUTRAL TO GROUND LINK ON ENCLOSURE (WHERE UFER BONDS TO CAN AND NEUTRAL)
07/23/2004 ELECTRIC - CABLE DROP Not ready for Inspection IVRS - Inspection :*