Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - ROUGH, SOIL
Permit Number - T03CM05672
Inspection Description - PLUMBING - ROUGH, SOIL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/08/2005 | PLUMBING - ROUGH, SOIL | Approved | IVRS - Inspection :* | |
01/31/2005 | PLUMBING - ROUGH, SOIL | Not ready for Inspection | IVRS - Inspection :* | |
01/28/2005 | PLUMBING - ROUGH, SOIL | Not ready for Inspection | IVRS - Inspection :* | |
11/19/2004 | PLUMBING - ROUGH, SOIL | Partial Approval | IVRS - Inspection :*/1)4" N/H ROOF DRAIN LEADER AT S.W. CORNER OK TO COVER | |
11/18/2004 | PLUMBING - ROUGH, SOIL | Partial Approval | IVRS - Inspection :*/1)INTERCEPTOR VENTS 3" N/H UP TO BLDG OK TO COVER. UNDERGROUND WATER TEST OK | |
11/16/2004 | PLUMBING - ROUGH, SOIL | Not ready for Inspection | IVRS - Inspection :* | |
11/16/2004 | PLUMBING - ROUGH, SOIL | Partial Approval | IVRS - Inspection :*/1)ROOF DRAIN LEADERS UNDERGROUND 6" AS "REDLINED" TO 12" SDR 35 TO MANHOLE. CONTRACTOR TO INSURE PRACTICAL ALIGINMENT BETWEEN SDR AND MH. SUBJECT TO APPROVED PLAN 2)INTERCEPTOR VENTS- ON 2" VENT NO MORE THAN 40' IN HORIZONTAL POSITION EXTERIOR DRAINS REQUIRE 12" MINIMUM COVER OR USE APPRVOED MAT'L. | |
11/15/2004 | PLUMBING - ROUGH, SOIL | Not ready for Inspection | IVRS - Inspection :*/1)UNABLE TO LOCATE GC 2)HOW ABOUT PROVIDING AN APPROVED PLAN AND TAKING CARE OF ALL THE LOOSE ENDS NOTED ABOVE. THIS JOB IS ON THE BRINK OF BEING OUT OF CONTROL AGAIN AND CONCERNS ME BECAUSE OF THE INCOMPLETE INSPECTIONS | |
11/02/2004 | PLUMBING - ROUGH, SOIL | Partial Approval | IVRS - Inspection :*/ROOF DRAIN LEADERS, UNDERGROUND, AS NOTED ON REDLINE DRAWING, OK TO COVER SUBJECT TO APPROVAL OF REDLINE DRAWING | |
08/12/2004 | PLUMBING - ROUGH, SOIL | Not ready for Inspection | IVRS - Inspection :SITE WATER COMPLETED | |
08/10/2004 | PLUMBING - ROUGH, SOIL | Not ready for Inspection | IVRS - Inspection :* | |
08/05/2004 | PLUMBING - ROUGH, SOIL | Not ready for Inspection | IVRS - Inspection :* | |
08/04/2004 | PLUMBING - ROUGH, SOIL | Not ready for Inspection | IVRS - Inspection :* | |
06/03/2004 | PLUMBING - ROUGH, SOIL | Partial Approval | IVRS - Inspection :*/ 4" RISERS ONLY ON 1ST FLOOR, SOIL ONLY - SEE PLAN P2-0. PLEASE NOTE INSP OF 3/8/04. | |
05/03/2004 | PLUMBING - ROUGH, SOIL | Partial Approval | IVRS - Inspection :*/ 1) 1ST FLOOR ROOF DRAINAGE AND DECK DRAINS ONLY STUB OUT AND 10' TEST PARTIAL SEE PLAN RED LINES ON JOB | |
03/18/2004 | PLUMBING - ROUGH, SOIL | Partial Approval | IVRS - Inspection 0000*/1) WRAP C.I. 1ST PHASE | |
03/11/2004 | PLUMBING - ROUGH, SOIL | Partial Approval | IVRS - Inspection 0000*/ GREASE LINE CENTERLINE 2.- PLEASE PROVIDE APPROVED REVISED PLAN FOR GREASE LINE NORTH OF C. AND CALL FOR 03005 FOR PRE-SLAB WRAP. | |
03/10/2004 | PLUMBING - ROUGH, SOIL | Partial Approval | IVRS - Inspection 0000*/ GREASE LINE NORTH TEST OK. | |
03/08/2004 | PLUMBING - ROUGH, SOIL | Partial Approval | IVRS - Inspection 0000*/ 1) PARTIAL APPROVAL ON GREASE LINE SUBJECT TO APPROVED REVISED PLAN. PLEASE NOTE: PROVIDE APPROVED PLANS AND PROPER PERMIT FOR SITE SEWER AND WATER | |
03/05/2004 | PLUMBING - ROUGH, SOIL | Partial Approval | IVRS - Inspection 0000*/ 1) UNDERGROUND SOIL ONLY-BLDG 1 WILL CALL FOR INSPECTION ON GREASE LINE WHEN READY | |
03/04/2004 | PLUMBING - ROUGH, SOIL | Not ready for Inspection | IVRS - Inspection 0000*/NR |