Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 02/11/2004 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection 0000*/ OK C OF O. |
| 02/10/2004 |
ELECTRIC - FINAL |
|
Partial Approval |
IVRS - Inspection 0000*/ COMPLETE EQUIP GROUNDING - RECALL WHEN DONE. |
| 02/09/2004 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0245*/ 1) INSTALL EQUIPMENT GROUNDS AS INDICATED ON PLANS FOR ALL POWER EQUIP. 2) DERATE CURRENT CARRING CONDUCTOR PER NEC 310, FOR AC, 480V AND 120V. 3) REVISE PLAN ONE LINE DIAGRAM FOR INSTALLATION OF DISC. S.W. INSTEAD OF MAIN BREAKER PANEL 'P'. |