Permit: T03CM05659

Parcel: 140374510


Addresses:

6211 E BRAMBLE ST

Inspection Status: Approved

Inspection History: FRAMING

Date Description Inspector Results Comments
04/05/2004 FRAMING Approved IVRS - Inspection 0000*
04/02/2004 FRAMING Partial Approval IVRS - Inspection 0000*/ 1) KING STUD FOR HD MISSING AT STAIRS AND HOLDWON NOT NAILED OR TIGHTENED 2) HD NOT NAILED RIGHT SIDE OF STAIRS
03/31/2004 FRAMING Denied IVRS - Inspection 0935*/ 1) NOTHING DONE FROM LAST INSPECTION 2) RE-FEE ASSESSED
03/30/2004 FRAMING Denied IVRS - Inspection 0999*/ 1) NAIL PROTECT PLUMBING AT POWDER ROOM, PLUMBING OUT OF WALL 2) HD MISSING, HD MISSING BOLT 3) SEAL PENETRATIONS INTO 2ND FLOOR AND ATTIC SPACE (FIRE BLOCK) 4) INSULATE BEHIND TUBS 5) SEE NOTES 1, 2 AND 3 FROM LAST INSPECTION 6) DO NOT INSULATE
03/25/2004 FRAMING Partial Approval IVRS - Inspection 0000*/ 1) H.D. MISSING BOLT/HD MISSING 2) FIREBLOCK MISSING AT WATER HEATER STAND 3) NAIL PROTECT ELECTRIC WITHIN 1 1/4 FROM EDGE 4) PROVIDE METAL COLLAR FOR B-VENT AT 2ND FLOOR CHAST TO ATTIC
03/24/2004 FRAMING Denied IVRS - Inspection 0999*/ 1) HOUSE NOT COMPLETE 2) NO TEST ON DWV'S 3) NO TEST ON WATER LINES 4) GAS TEST AT 7 PSI, 10 PSI RED 5) STOPPED INSPECTION-HAVE TRADES AND SUPERVISOR WALK HOUSE BEFORE RECALL FOR INSPECTION