Permit: T03CM05655


Addresses:

9348 E RITA RD


Inspection Status: Approved

Inspection History: PLUMBING - YARD WTR LINE/TEST

Permit Number - T03CM05655

Inspection Description - PLUMBING - YARD WTR LINE/TEST

Inspection Status - Approved

Date Description Inspector Results Comments
06/02/2005 PLUMBING - YARD WTR LINE/TEST Approved IVRS - Inspection :*
04/08/2005 PLUMBING - YARD WTR LINE/TEST Not ready for Inspection IVRS - Inspection :*
09/28/2004 PLUMBING - YARD WTR LINE/TEST Partial Approval IVRS - Inspection :*/100 PSI AIR TEST FROM (3) METERS- 1 1/2 YARD LINES TO EACH OF (3) SEPERATE BUILDING SERVICE ENTRANCES (PARTIAL) 1)WILL NEED TO SEE CONNECTION FROM PVC TO (3) BACKFLOW DEVICES AT METER LOCATIONS WITH METER INSTALLATION.
09/22/2004 PLUMBING - YARD WTR LINE/TEST Not ready for Inspection IVRS - Inspection :*/1)03055-HAVE YOUR PLAN REVISED & CITY APPROVED WITH ACTUAL INSTALLATION OF BUILDING DRAINS AT HCS CONNECTION. 2)03040-USE APPROVED FITTINGS FOR CHANGES OF DIRECTION. 3)HAVE YOUR PLAN REVISED & CITY APPROVED WITH ACTUAL INSTALLATION OF YARD WATER PIPING FROM METER, THRU BACKFLOW DEVICE TO BUILDING SERVICE ENTRANCE