Permit: T03CM05655


Addresses:

9348 E RITA RD


Inspection Status: Approved

Inspection History: PLUMBING - ROUGH, SOIL

Permit Number - T03CM05655

Inspection Description - PLUMBING - ROUGH, SOIL

Inspection Status - Approved

Date Description Inspector Results Comments
09/20/2004 PLUMBING - ROUGH, SOIL Approved IVRS - Inspection :*
08/26/2004 PLUMBING - ROUGH, SOIL Denied IVRS - Inspection :
See detailed listing on site.| 999*/DENIED
PROVIDE PERMIT CARDS WITH CORRECT ADDRESS AND HAVE CORRECT ADDRESS POSTED AT SITE ON BUILDINGS.
08/20/2004 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :8"SAR 35.4 PSI AIR TEST FROM MANHOLE#1 TO MANHOLE#2 OK
HANDROLL PULL FROM MANHOLE#1 TO MANHOLE#2 OK
8"SAR 35 4#PSI AIR TEST FROM MANHOLE#3 TO MANHOLE#4 INCLUDING 4"HCS CONNECTION TO NORTHWEST CORNER 5' FROM BUILDING HAS TRANSITION TO 4" DUCTILE IRON 10' EACH SIDE OF CROSSING 1' UNDER 8" 900 WATER MAIN, THIS REQUIRES CITY APPROVED DETAIL DRAWING AT BOTH WEST SIDE LOCATION
STILL NEED VACUUM TESTING OF ALL MANHOLES AND AIR TEST ON 4" FROM MANHOL #4 TO SOUTHWEST BLD, HCS CONNECTION
08/19/2004 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*/ 1) MANHOLE #3 TO MANHOLE #5 4 PSI AIR TEST ON 8" SDR 35 AND (2) 2) 4" SDR 35 LATERALS TO 5' FROM BLDG OK 3) MANHOLE #2 TO MANHOLE #3 4 PSI AIR TEST ON 8" SDR 35 OK
08/16/2004 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
08/04/2004 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :NEW MANHOLE #1 ON EXISTING 10", 8" DUCTILE IRON UP STREAM TO MANHOLE #2, 8" SDR35, UPSTREAM TO MANHOLE #3, 8" SDR35 UP STREAM TO SOUTH TO MANHOLE #4, 8" FROM SDR35 MANHOLE #3 TO EAST MANHOLE #5 OK
WILL NEED TO SEE IN WRITING CERTIFICATE OF CONFORMANCE (PIMA cOUNTY) OR LETTER FROM THOM STATING IS NOT NECESSARY
CONTRACTOR TO AIR TEST PIPING & VACUUM TEST MANHOLES AT LATER DATE
NEED FITTINGS INSTALLED FOR HCS CONNECTIONS
NEED REVISED CITY APPROVED PLAN FOR HCS PIPING CROSSING WATER MAIN ON WEST SIDE OF BUILDIN (2) LOCATIONS
WILL NEED TO SEE MANDREL PULL AT LATER DATE
07/27/2004 PLUMBING - ROUGH, SOIL Not ready for Inspection IVRS - Inspection :*NOT READY. PRE-CON MEET WITH SITE SEWER INSTALLER.