Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
| Date |
Description |
Inspector |
Results |
Comments |
| 04/20/2004 |
PLUMBING - INTERMEDIATE |
|
Approved |
IVRS - Inspection 0000*/ 1) CORRECTIONS MADE OK. 2) OK TO COVER ALL AREAS. |
| 04/19/2004 |
PLUMBING - INTERMEDIATE |
|
Denied |
IVRS - Inspection 0999*/ 1) YOU MAY NOT RUN A WTR LINE OVER AN ELECTRIC SERVICE PANEL. 2) ALL HORIZONTAL VENT PIPING TO BE INSTALLED LEVEL OR TO DRAIN BACK TO FIXTURE. 3) SUPPORT UPSTAIRS CLOSET BEND. 4) COMPLETELY REMOVE ALL SILICONE FROM CLEAN OUTS AND RE-INSTALL WITH APPROVED TAPE OR COMPOUND. 5) SEE INSTALLATION STANDARD 15.9 PVC DWV 94 UPC...TO BE SUPPORTED AT END OF BRANCHES AND THE CHANGE OF ELEVATION OR DIRECTION AND THEN EVERY 4 FEET MAX. 6) PVC WTR TEST OK. PEX PRESSURE TEST OK. |
| 04/16/2004 |
PLUMBING - INTERMEDIATE |
|
Denied |
IVRS - Inspection 0999*/ 1) I HAVE A CONCERN. I NOTICED SEVERAL BUSHINGS ONLY PARTIALLY SOCKETED. IF YOU ARE NOT FULLY SOCKETING THE BUSHINGS, WHAT OTHER FITTINGS ARE ONLY PARTIALLY SOCKETED? 2) WHEN RUNNING A TRAP ARM OFF OF A 3" STACK, INSTALL THE CORRECT FITTING - MULTIPLE BUSSHINGS NOT ACCEPTED. 3) UPSTAIRS REVENT BACKPITCHED. |