Inspection Status: Approved
Inspection History: FRAMING
| Date |
Description |
Inspector |
Results |
Comments |
| 03/29/2004 |
FRAMING |
|
Approved |
IVRS - Inspection 0000* |
| 03/26/2004 |
FRAMING |
|
Denied |
IVRS - Inspection 0999*/ 1) SECURE AND INSULATE A/C LINES IN 1ST FLOOR CLOSET |
| 03/25/2004 |
FRAMING |
|
Denied |
IVRS - Inspection 0999*/ 1) PROTECT WIRING AND PEX FROM FLOOR TRUSS GUSSETS 2) SECURE A/C LINES IN CLOSET ACCROSS FROM LAUNDRY AND INSULATE LINE 3) SHIM HEADER WHERE NEEDED-MANY 4) REPLACE CUT KINGS UNDER GIRDER AT BOTTOM OF STAIRS 5) FIRE BLOCK DUCT CHASE IN S.W. BED CLOSET AND FLU CHASE IN MASTER CLOSET AND ABOVE MASTER TUB AND HALL DUCT CHASE |