Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO.
If you cannot find what you are looking for please
submit a records request.
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 01/08/2004 |
MECHANICAL - FINAL |
|
Approved |
IVRS - Inspection 0000*/ 1) CORRECTIONS HAVE BEEN MADE. LEFT GAS CARD |
| 01/07/2004 |
MECHANICAL - FINAL |
|
Denied |
IVRS - Inspection 0999*/ 15 PSI TEST IS OK. / 1) PROVIDE MIN. 1" CLEARANCE FROM COMBUSTABLE ON WTR HTR VENT. SCREW DRAFT DIVERTER TO TOP OF WTR HTR AND USE MIN. 3 SCREWS IN EACH JOINT OF VENT CONNECTOR. INNER LINER OF VENT PIPE HAS SEERATED. REPLACE DOUBLE WALL PIPE TO WTR HTR AND EXTEND 2' ABOVE WALL ON ROOF. 2) EXTEND FURNACE VENT 2' ABOVE EVAP COOLER. RECALL FOR INSPECTION. ALSO PROVIDE 1" CLEARANCE WHERE FURNACE VENT PENETRATES THE ROOF. |
| 01/05/2004 |
MECHANICAL - FINAL |
|
Denied |
IVRS - Inspection 0999*/ 1) PROVIDE ACCESS TO ROOF. 2) PROVIDE MIN. 10 LB PRESSURE TEST. NEW WTR HTR INSTALLED WITHOUT A PERMIT. PROVIDE NECESSARY PERMIT AND CALL FOR INSP. |