Permit: T03CM05619

Parcel: 117050520


Addresses:

311 E 7TH ST


Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Permit Number - T03CM05619

Inspection Description - MECHANICAL - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
01/08/2004 MECHANICAL - FINAL Approved IVRS - Inspection 0000*/ 1) CORRECTIONS HAVE BEEN MADE. LEFT GAS CARD
01/07/2004 MECHANICAL - FINAL Denied IVRS - Inspection 0999*/ 15 PSI TEST IS OK. / 1) PROVIDE MIN. 1" CLEARANCE FROM COMBUSTABLE ON WTR HTR VENT. SCREW DRAFT DIVERTER TO TOP OF WTR HTR AND USE MIN. 3 SCREWS IN EACH JOINT OF VENT CONNECTOR. INNER LINER OF VENT PIPE HAS SEERATED. REPLACE DOUBLE WALL PIPE TO WTR HTR AND EXTEND 2' ABOVE WALL ON ROOF. 2) EXTEND FURNACE VENT 2' ABOVE EVAP COOLER. RECALL FOR INSPECTION. ALSO PROVIDE 1" CLEARANCE WHERE FURNACE VENT PENETRATES THE ROOF.
01/05/2004 MECHANICAL - FINAL Denied IVRS - Inspection 0999*/ 1) PROVIDE ACCESS TO ROOF. 2) PROVIDE MIN. 10 LB PRESSURE TEST. NEW WTR HTR INSTALLED WITHOUT A PERMIT. PROVIDE NECESSARY PERMIT AND CALL FOR INSP.