Permit: T03CM05616

Parcel: 119032410


Addresses:

506 W 42ND ST

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
12/10/2003 PLUMBING - FINAL Approved IVRS - Inspection 0000*/ 1) GAS PRESSURE TEST IS OK 2) GAS SHUT OFF VALVES OK 3) WATER HEATER FLU VENT, T & P VALVE AND DRAIN IS OK
12/04/2003 PLUMBING - FINAL Denied IVRS - Inspection 0999*/ 1) MUST EXTEND T&P DRAIN FOR WTR HTR TO DAYLIGHT. 2) MUST PROVIDE A AGA SHUT OFF VALVE FOR FIREPLACE. 3) MUST CAP OFF ALL SUPPLYS THAT DO NOT HAVE APPLIANCES. 4) MUST PROVIDE AIR PRESSURE TEST ON SYSTEM - 10 LBS MIN. 5) MUST PROVIDE 2 - 10X10 LOUVER GRILLS FOR WTR HTR ENCLOSURE.