Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO.
If you cannot find what you are looking for please
submit a records request.
PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.
Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
| Date |
Description |
Inspector |
Results |
Comments |
| 04/05/2004 |
PLUMBING - INTERMEDIATE |
|
Approved |
IVRS - Inspection 0000*/ 1) CORRECTIONS MADE OK. 2) OK TO COVER ALL AREAS. |
| 04/02/2004 |
PLUMBING - INTERMEDIATE |
|
Not ready for Inspection |
IVRS - Inspection 0000*/ 1) NOT INSTALLED PER PLAN REQUIRE TYPE 'L' COPPER NOT PEX. 2) ALL HORIZONTAL PVC ABOVE CEILING TO BE SUPPORTED. 3) A TRAP ARM MAY ONLY CHANGE DIRECTION 90o WITHOUT ADDITIONAL C.O. 4) ON DRAINAGE PIPING, HORIZONTAL X HORIZONTAL CHANGE OF DIRECTION TO BE WYR BRANCH OR EQUIVELENT. 5) SECURE UPSTAIRS CLOSET FLANGE. |