Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
| Date |
Description |
Inspector |
Results |
Comments |
| 04/05/2004 |
PLUMBING - INTERMEDIATE |
|
Approved |
IVRS - Inspection 0000*/ 1) CORRECTIONS MADE OK. 2) OK TO COVER ALL AREAS. |
| 04/02/2004 |
PLUMBING - INTERMEDIATE |
|
Not ready for Inspection |
IVRS - Inspection 0000*/ 1) NOT INSTALLED PER PLAN REQUIRE TYPE 'L' COPPER NOT PEX. 2) ALL HORIZONTAL PVC ABOVE CEILING TO BE SUPPORTED. 3) A TRAP ARM MAY ONLY CHANGE DIRECTION 90o WITHOUT ADDITIONAL C.O. 4) ON DRAINAGE PIPING, HORIZONTAL X HORIZONTAL CHANGE OF DIRECTION TO BE WYR BRANCH OR EQUIVELENT. 5) SECURE UPSTAIRS CLOSET FLANGE. |