Permit: T03CM05614

Parcel: 123172510


Addresses:

1402 E LEE ST #01

Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Date Description Inspector Results Comments
04/05/2004 PLUMBING - INTERMEDIATE Approved IVRS - Inspection 0000*/ 1) CORRECTIONS MADE OK. 2) OK TO COVER ALL AREAS.
04/02/2004 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection 0000*/ 1) NOT INSTALLED PER PLAN REQUIRE TYPE 'L' COPPER NOT PEX. 2) ALL HORIZONTAL PVC ABOVE CEILING TO BE SUPPORTED. 3) A TRAP ARM MAY ONLY CHANGE DIRECTION 90o WITHOUT ADDITIONAL C.O. 4) ON DRAINAGE PIPING, HORIZONTAL X HORIZONTAL CHANGE OF DIRECTION TO BE WYR BRANCH OR EQUIVELENT. 5) SECURE UPSTAIRS CLOSET FLANGE.