Permit: T03CM05611

Parcel: 141011980


Addresses:

5306 S CIVANO BL


Inspection Status: Approved

Inspection History: EXT METAL CLIPS/EXT SHEATHING

Permit Number - T03CM05611

Inspection Description - EXT METAL CLIPS/EXT SHEATHING

Inspection Status - Approved

Date Description Inspector Results Comments
04/07/2004 EXT METAL CLIPS/EXT SHEATHING Approved IVRS - Inspection 0000*
03/12/2004 EXT METAL CLIPS/EXT SHEATHING Partial Approval IVRS - Inspection 0000* HANGER SIZE NOT ON PLAN. YOU USED A AUZ/OR (ADVANCE TYPE). YOU INSTALLED 10D NAILS, THIS HANGER GIVES LOAD VALUE FOR 10 D'S @ 1,555, 16D'S @ 1,860 WHAT IS REQD? IS THE EXISTING DECK TO BE USED AS WALKING DECK, IF SO INFORMATION MISSING. PLAN CALLS FOR TWO 1/2" 0 LAGS EACH STUD, YOU HAVE ONE. PLEASE BACK ONE LAG OUT TO CHECK SIZE. BOTTOM POST BASES REQUIRE 16 D'S.