Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - TEMPORARY SERVICE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/03/2006 | ELECTRIC - TEMPORARY SERVICE | Approved | IVRS - Inspection :*TEMP CONST POWER 'NO CIRCUITS BEYOND GFI RECEPTACLE AT PANEL TO BE ENERGIZED |
|
| 02/02/2006 | ELECTRIC - TEMPORARY SERVICE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. INSTALL MISSING BOND SCREW AT NEUTRAL (AT MAIN DISCONNECT SWITCH) 2. TIGHTEN ALL LOCKNUTS TIGHT 3. INSTALL 2" LOCKNUT AT INSIDE OF DISCONNECT SWITCH ON OFFSET NIPPLE & INSIDE METER BASE CABINET 4. SET SCREWS ARE MISSING AT BONDING BUSHINGS (THROUGHOUT) 5. ISOLATE NEUTRAL FROM GROUNDING CONDUCTORS AT SUB PANEL |
|
| 01/25/2006 | ELECTRIC - TEMPORARY SERVICE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) BOND WATER PIPING 2) BOND BUSHINGS REQUIRED ON SUPPLY SIDE OF SERVICE 3) INSTALL REJECTION PINS, BOND NEUTRAL TO ENCLOSURE AND MAIN BOND SCREW IN SERVICE DISCONNECT 4) INSTALL PERMANENT ADDRESS LABEL 5) VERIFY L-11 LICENSED CONTRACTOR NAME AND PHONE NUMBER |