Permit: T03CM05592

Parcel: 123050870


Addresses:

2130 E HAMPTON ST

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
10/07/2004 ELECTRIC - FINAL Approved IVRS - Inspection :*
10/05/2004 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*/ 1) SUB-PANEL MUST HAVE GROUNDED GROUND BAR WITH ISOLATED NEUTRAL BAR ALL COPPER GROUNDS 90 ON GROUND AND ALL WHITE NEUTRAL 90 ON NEUTRAL BAR 2) ALL GARAGE CONVENIENCE OUTLETS BELOW 6'-8" MUST BE GFCI PROTECTION 3) DRYER CIRCUIT MUST USE A-4 WIRE OUTLET 4) 3 PT BEARING TRUSSES MUST BEAR ON
09/15/2004 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*/ 1) CHANGE FROM ? TO UE SERVICE 2) ADD CABLE DROP