Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - UNDERGROUND
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/13/2004 | ELECTRIC - UNDERGROUND | Approved | IVRS - Inspection :* | |
| 07/30/2004 | ELECTRIC - UNDERGROUND | Partial Approval | 1) PVC FOR PANEL FEEDS-OK | |
| 07/29/2004 | ELECTRIC - UNDERGROUND | Partial Approval | DO NOT HEAT PVC WITH TORCH USE BELL ENDS IN CABINET OR BUSHING |
|
| 07/15/2004 | ELECTRIC - UNDERGROUND | Partial Approval | INSIDE 4 PVC'S 3/4" OK TO COVER | |
| 06/02/2004 | ELECTRIC - UNDERGROUND | Partial Approval | FINISH TAPING THREADS AT STTET TO PVC. 1) ACORN CLAMP NOT SIZED PER 3/0 COPPER REBAR TO BE TIED INTO WHOLE SYSTEM. 2) THREADS ON STEEL CONDUIT SHOULD BE TAPED COMPLETE - NO THREADS SHOWING. |