Permit: T03CM05566

Parcel: 141173840

Inspection Status: Approved

Inspection History: FRAMING

Date Description Inspector Results Comments
02/25/2004 FRAMING Approved IVRS - Inspection 0000*
02/24/2004 FRAMING Denied IVRS - Inspection 0999*
02/24/2004 FRAMING Not ready for Inspection IVRS - Inspection 0000*/ 1) SEE MARKS ON FLOOR MISSING BACKING AND LOOSE BOTTOM PLATES 2) SHORT NAILED STC 24 TRUSS CLIPS 3) NEED WATER TEST DWV 4) STRAP AT DRYER DUCT T-PLATE 5) GAS PRESSURE OK 6) POTABLE WATER OK 7) HALL TUB WET TUB AT SHOE 8) NEED ANCHOR BOLTS 1/2 DIAMETER 24" ON CENTER SW5 GARAGE
02/20/2004 FRAMING Cancelled IVRS - Ri canceled