Permit: T03CM05556

Parcel: 138133400

Inspection Status: Approved

Inspection History: FRAMING

Date Description Inspector Results Comments
04/06/2004 FRAMING Approved IVRS - Inspection 0000*
04/02/2004 FRAMING Denied IVRS - Inspection 0999*/ 1) SEAL FIRE STOP ALL 2ND FLOOR PENETRATIONS 2) GARAGE SHEAR WALL NOT NAILED TO STUDS AT HOLDOWN 3) 2/SD2 NOT COMPLIED WITH 4) 10/SD4 NOT COMPLIED WITH 5) INSTALL BUSHING/ROMEX CLAMP AT FIRE PLACE 6) BEARING WALL REQUIRES STUDS AT 16" OK 7) OVER NOTCHED BEARING DOUBLE TOP PLATES BY ENTRY. INSTALL 2 FHA STRAP 8) STAIR WINDER MUST BE 6" ON NARROW END 9) ANCHOR W/C FLOOR FLANGES 10) FLOOR MISSING SCREWS 11) A/C DISCONNECT MISSING 12) EXT WALL PLATE REQUIRED 16D AT 16" ON CENTER 13) STAIR LIGHT AND BELL TOO LOW 6'-8" PLUS
03/08/2004 FRAMING Not ready for Inspection IVRS - Inspection 0000* WILL NOT INSPECT INTERMEDIATES UNTIL PROOF OF EXT CLIP APPROVED. 1) PROVIDE PROOF OF ROOF & CLIP INSPECTION APPROVAL. 2) 4 TRUSSES WEST END OF GARAGE NOT CLIPPED. 3) 10/5P4 NOT COMPLIED WITH. 4) 11/5D4 NOT COMPLIED WITH.