Inspection History: ELECTRIC - CABLE DROP
Permit Number - T03CM05524
Inspection Description - ELECTRIC - CABLE DROP
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/18/2004 | ELECTRIC - CABLE DROP | Approved | IVRS - Inspection :* | |
| 04/23/2004 | ELECTRIC - CABLE DROP | Denied | IVRS - Inspection : See detailed listing on site.| 999*/ 1) 480 VOLT SERVICE REQUIRES A NEUTRAL 2) INSTALL A MAIN BONDING JUMPER AT MAIN.480 VOLT DISCONNECT AND BOND GREEN SCREEW 3) OLD SERVICE AREA IS NOW SUB EQUIPMENT THE OLD EXIST DISCONNECT IS SERVICE EQUIPMENT RATED, NO ISLOATION OCCURS AT THIS POINT AND WIRING SPACE IS ?. REQUESTING THAT THIS DISCONNECT BE REPLACED. 7204 SERVICE REQUIRES NEUTRAL ISOLATE SUB EQUIPMENT-OTHER |