Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 12/03/2003 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection 0000* |
| 11/28/2003 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0210*/ 1) PUT ADDRESS I.D. ON EACH METER CAN. 2) I.D. TRAY ON EACH SWITCH DISCONNECT - PNL A-B. 3) REJECTION PINS IN EACH MAIN DISCONNECT. 4) I.D. PANELS INSIDE BLDG A-B. 5) REVISE PLAN - POWER RISER DIAGRAM MUST REFLECT THE PARALLEL. 6) REPLACE LAST SECTION OF EMT WITH FLEX CONDUIT AT PUNCH MACHINE. |
| 11/25/2003 |
ELECTRIC - FINAL |
|
Not ready for Inspection |
IVRS - Inspection 0000* |