Permit: T03CM05484

Parcel: 10707007D

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
12/03/2003 ELECTRIC - FINAL Approved IVRS - Inspection 0000*
11/28/2003 ELECTRIC - FINAL Denied IVRS - Inspection 0210*/ 1) PUT ADDRESS I.D. ON EACH METER CAN. 2) I.D. TRAY ON EACH SWITCH DISCONNECT - PNL A-B. 3) REJECTION PINS IN EACH MAIN DISCONNECT. 4) I.D. PANELS INSIDE BLDG A-B. 5) REVISE PLAN - POWER RISER DIAGRAM MUST REFLECT THE PARALLEL. 6) REPLACE LAST SECTION OF EMT WITH FLEX CONDUIT AT PUNCH MACHINE.
11/25/2003 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection 0000*