Permit: T03CM05472

Parcel: 10511061R

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
03/17/2004 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection 0000*
03/16/2004 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*/ WALL ROUGH IN ONLY. 1) THE NE CODE REQUIRES M/C CABLE BE STRAPED, OR TIE WIRED WITHIN 12" OF EACH BOX, FIXTURE ETC. THE M/C CABLE IN THE FRONT SOFFIT REQUIRES SUPPORT. 2) INSTALL THE CIRCUITS AND J-BOXES FOR THE SIGN CIRCUIT. DO NOT DEVIATE FROM THE ENGINEERS CIRCUIT LAYOUT. DISTRIBUTION OF CIRCUITS MUST BE PER PANEL SCHEDULE. RECALL FOR HARD CEILING INSP. PRIOR TO APPLYING DRYWALL.