Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T03CM05472
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/17/2004 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection 0000* | |
03/16/2004 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*/ WALL ROUGH IN ONLY. 1) THE NE CODE REQUIRES M/C CABLE BE STRAPED, OR TIE WIRED WITHIN 12" OF EACH BOX, FIXTURE ETC. THE M/C CABLE IN THE FRONT SOFFIT REQUIRES SUPPORT. 2) INSTALL THE CIRCUITS AND J-BOXES FOR THE SIGN CIRCUIT. DO NOT DEVIATE FROM THE ENGINEERS CIRCUIT LAYOUT. DISTRIBUTION OF CIRCUITS MUST BE PER PANEL SCHEDULE. RECALL FOR HARD CEILING INSP. PRIOR TO APPLYING DRYWALL. |