Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T03CM05469
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/07/2004 | ELECTRIC - INTERMEDIATE | Approved | ||
06/08/2004 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :*/ OK BAR AREA. | |
06/04/2004 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :*/ 1) USE APPROVED STRAPS OR METHODS TO SECURE M/C TO STUD. 2) PROTECT CABLES AND FLEX CONDUITS IN STUD CHANNELS. OK WALLS AT BAR AREA AND PANEL WALL TO TOP OF PANEL. | |
05/28/2004 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :*/ PROTECT VDV CABLES FROM SHARP METAL EDGES AND AT SHALLOW STUDS. OK EXTERIOR WALL EXCEPT AS NOTED. | |
05/24/2004 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :*/ OK ABOVE BARRIER PAPER CEILING. |