Permit: T03CM05463

Parcel: 108163150

Inspection Status: Approved

Inspection History: BUILDING - FINAL

Date Description Inspector Results Comments
04/29/2004 BUILDING - FINAL Approved IVRS - Inspection :
See detailed listing on site.| 999*
04/28/2004 BUILDING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
04/27/2004 BUILDING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*/ 1) NO WEATHER CAPS ON 'B' VENTS 2) NO SPARK SHIELD/CAP ON FIRE PLACE 3) FIRE PLACE AND EXTEND 2 FEET HIGHER THAN ROOF WITHIN 10 FEET 4) SECURE A/C WHIP WITHIN 12" OF DISCONNECT 5) NO POWER TO OUTSIDE GFCI RECEPTACLES 6) STOPPED INSPECTION. TOO MANY ITEMS