Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - UNDERGROUND
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/05/2004 | ELECTRIC - UNDERGROUND | Approved | IVRS - Inspection :* | |
| 09/30/2004 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :*APPROVED. | |
| 09/24/2004 | ELECTRIC - UNDERGROUND | Denied | IVRS - Inspection : See detailed listing on site.| 999*/ 1) SERVICE NOT INSTALLED OR REFLECTIVE OF PLANS AND REV #1 2) CHASE NIPPLE NOT APPROVED FITTING FOR USE WITH LB 3) LABEL PANELS AND BREAKERS 4) WE HAVE UNSAFE EXPOSED CONDUCTORS IN WOOD FRAMED PANEL ENCLOSURE 5) PLEASE VERIFY SCHEDULE 80 PVC ABOVE GRADE 6) TIGHTEN LOOSE FITTINGS 7) DERATE FOR CONDUCTOR FILL 310.15 8) NO VERIFICATION OF GROUNDING SUPLIMETAL CONDUCTOR AT POLE BASES-POURED WITHOUT INSPECTION ? 9) NO POLES INSTALLED AT THIS TIME 10) SUPPORT EMT CONDUIT AS PER CODE 11) WALL PACK TO MEET LIGHTING CODE SIZE 5 |
|
| 08/11/2004 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :*/PERIMETER PVC OK TO COVER. CALL FOR UFER INSPECTION OF POLE BASES. | |
| 08/10/2004 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :*/PARTIAL- FRONT TRENCH-SOUTH LOT OK TO COVER PUC. |