Inspection History Details
Inspection Status: Approved
Inspection History: EXT METAL CLIPS/EXT SHEATHING
Permit Number - T03CM05443
Inspection Description - EXT METAL CLIPS/EXT SHEATHING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/16/2004 | EXT METAL CLIPS/EXT SHEATHING | Approved | IVRS - Inspection 0000*/ 1) NOTE: HANGERS NOT INSTALLED FOR LIVING ROOM. LEAVE TEMP WALL STANDING | |
03/29/2004 | EXT METAL CLIPS/EXT SHEATHING | Partial Approval | IVRS - Inspection 0000*/ 1) HANGER SIZE ON PLAN GARAGE, TRUSSES BOTH SIDES OF I BEAM 2) MISSED P.A. NEED RETRO FIT TYPE | |
01/15/2004 | EXT METAL CLIPS/EXT SHEATHING | Not ready for Inspection | IVRS - Inspection 0000*/ 1) NO DETAIL FOR GARAGE BEAM HANGERS, ROOF JOG ABOVE 2) NO DETAIL FOR CENTER BEARING TRUSS TO TRUSS CONNECTION 3) 4/SD4 CALLS FOR PANELS BETWEEN TRUSSES QUEST. SPACE AT EXTERIOR WALLS BETWEEN FLOORS IS A PLYWOOD BAND REQUIRED ACROSS SPACE, PERPENDICULAR AND PARALELL 4) CONTINUE BEARING FROM FLOOR TO FLOOR CONCENTRATED LOAD 5) SHEAR AT SLIDER TO CONTINUE TO H.D. 6) NEED A DETAIL SHOWING SNUB NOSE TRUSSES 1/SD3 6) INSTALL ALL SHEAR PANELS BETWEEN TRUSSES 7) INSTALL ALL TRUSS LATERAL BRACES 8) INSTALL ALL END GABLE KICK BRACES 9) NEED REAR DECK PLAN RAILING 10) BLOCK UNDER END OF PLY ROOF 8' 11) OK TO DRY IN DON'T LOAD |