Permit: T03CM05430

Parcel: 138243410

Inspection Status: Approved

Inspection History: BUILDING - FINAL

Date Description Inspector Results Comments
02/26/2004 BUILDING - FINAL Approved IVRS - Inspection 0000*
02/25/2004 BUILDING - FINAL Denied IVRS - Inspection 0950*/ 1) FILL OPEN KNOCK OUT IN ELECTRIC PANEL 2) LABEL ALL CIRCUITS IN ELECTRIC PANEL 3) SECURE ELECTRIC PANEL DEAD FRONT WITH PROPER SCREWS 4) EXCESSIVE OVER CURRENT PROTECTION FOR A/C CONDENSOR, MAXIMUM ALLOWED 40 AMP. 50 AMP INSTALLED 5) NO POWER TO OUTSIDE GFCI CIRCUITS 6) ELECTRIC OUTLETS GREATER THAN 24" FROM KITCHEN COUNTER ENDS 7) STOPPED INSPECTION. TOO MANY ITEMS